Specifications
Model |
SUN-5K-SG04LP3-EU |
SUN-6K-SG04LP3-EU |
SUN-8K-SG04LP3-EU |
SUN-10K-SG04LP3-EU |
SUN-12K-SG04LP3-EU |
Battery Input Data |
Battery Type |
Lead-acid or Lithium-ion |
Battery Voltage Range (V) |
40~60 |
Max. Charging Current (A) |
120 |
150 |
190 |
210 |
240 |
Max. Discharging Current (A) |
120 |
150 |
190 |
210 |
240 |
Charging Curve |
3 Stages / Equalization |
External Temperature Sensor |
Yes |
Charging Strategy for Li-Ion Battery |
Self-adaption to BMS |
PV String Input Data
Max. DC Input Power (W) |
6500 |
7800 |
10400 |
13000 |
15600 |
Rated PV Input Voltage (V) |
550(160~800) |
Start-up Voltage (V) |
160 |
MPPT Voltage Range (V) |
200-650 |
Full Load DC Voltage Range (V) |
350-650 |
PV Input Current (A) |
13+13 |
26+13 |
Max. PV ISC (A) |
17+17 |
34+17 |
No.of MPP Trackers |
2 |
No.of Strings per MPP Tracker |
1+1 |
2+1 |
AC Output Data
Rated AC Output Active Power (W) |
5000 |
6000 |
8000 |
10000 |
12000 |
Max AC Output Active Power (W) |
5500 |
6600 |
8800 |
11000 |
13200 |
AC Output Rated Current (A) |
7.6/7.2 |
9.1/8.7 |
12.1/11.6 |
15.2/14.5 |
18.2/17.4 |
Max AC Output Current (A) |
8.4/8 |
10/9.6 |
13.4/12.8 |
16.7/15.9 |
20/19.1 |
Max. Three-phase Unbalanced Output Current (A) |
11.4/10.9 |
13.6/13 |
18.2/17.4 |
22.7/21.7 |
27.3/26.1 |
Max Output short circuit current (A)Â |
70 |
Max. Continuous AC Passthrough (A) |
45 |
Peak Power (off grid) |
2 time of rated power, 10 S |
Power Factor Adjustment Range |
0.8 leading to 0.8 lagging |
Rated Input/Output Voltage/Range(V) |
220/380, 230/400 0.85Un-1.1Un |
Rated Input/Output Grid Frequency/Range |
50Hz/45Hz-55Hz 60Hz/55Hz-65Hz |
Grid Connection Form |
3L+N+PE |
Total Harmonics Current Distortion (THDi) |
<3% (of nominal power) |
DC Current Injection |
<0.5% In |
Efficiency
Max. Efficiency |
97.60% |
Euro Efficiency |
97.00% |
MPPT Efficiency |
99.90% |
Protection
Integrated |
Anti-islanding Protection, PV String Input Reverse Polarity Protection,
Insulation Resistor Detection, Residual Current Monitoring Unit, Output Over Current Protection,
Output Shorted Protection, Surge Protection |
Surge protection |
DC Type III / AC Type III |
Over Voltage Category |
DC Type II/AC Type III |
Certifications and Standards
Grid Regulation |
IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002,
OVE-Richtlinie R25, G99, VDE-AR-N 4105 |
Safety EMC / Standard |
IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 |
General Data
Operating Temperature Range (℃) |
-40 to +60℃, >45℃ Derating |
Cooling |
Smart Cooling |
Noise (dB) |
≤45 dB |
Communication with BMS |
RS485; CAN |
Weight (kg) |
33.6 |
Cabinet Size (WxHxD mm) |
422×702×281 (Excluding Connectors and Brackets) |
Protection Degree |
IP65 |
Installation Style |
Wall-mounted |
Warranty |
5 Years/10 Years
the Warranty Period Depends the Final Installation Site of Inverter, More Info Please Refer to Warranty Policy |